1、Thermal comfort in the future - Excellence and expectationP. Ole Fanger and Jørn ToftumInternational Centre for Indoor Environment and EnergyTechnical University of DenmarkAbstractThis paper predicts some trends foreseen in the new century as regards the indoor environment and thermal comfort.
2、One trend discussed is the search for excellence, upgrading present standards that aim merely at an “acceptable” condition with a substantial number of dissatisfied. An important element in this connection is individual thermal control. A second trend is to acknowledge that elevated air temperature
3、and humidity have a strong negative impact on perceived air quality and ventilation requirements. Future thermal comfort and IAQ standards should include these relationships as a basis for design. The PMV model has been validated in the field in buildings with HVAC systems that were situated in cold
4、, temperate and warm climates and were studied during both summer and winter. In non-air-conditioned buildings in warm climates occupants may sense the warmth as being less severe than the PMV predicts, due to low expectations. An extension of the PMV model that includes an expectancy factor is prop
5、osed for use in non-air-conditioned buildings in warm climates. The extended PMV model agrees well with field studies in on-air-conditioned buildings of three continents.Keywords: PMV, Thermal sensation, Individual control, Air quality, AdaptationA Search for ExcellencePresent thermal comfort standa
6、rds (CEN ISO 7730, ASHRAE 55) acknowledge that there are considerable individual differences between peoples thermal sensation and their discomfort caused by local effects, i.e. by air movement. In a collective indoor climate, the standards prescribe a compromise that allows for a significant number
7、 of people feeling too warm or too cool. They also allow for air velocities that will be felt as a draught by a substantial percentage of the occupants.In the future this will in many cases be considered as insufficient. There will be a demand for systems that allow all persons in a space to feel co
8、mfortable. The obvious way to achieve this is to move from the collective climate to the individually controlled local climate. In offices, individual thermal control of each workplace will be common. The system should allow for individual control of the general thermal sensation without causing any
9、 draught or other local discomfort. We know the range of operative temperatures required in a workplace to satisfy nearly everybody (Wyon 1996; Fanger 1970) and we know the sensitivity to draught from a wide range of studies. A search for excellence involves providing all persons in a space with the
10、 means to feel thermally comfortable without compromise.Thermal Comfort and IAQPresent standards treat thermal comfort and indoor air quality separately, indicating that they are independent of each other. Recent research documents that this is not true (Fang et al. 1999; Toftum et al. 1998). The ai
11、r temperature and humidity combined in the enthalpy have a strong impact on perceived air quality, and perceived air quality determines the required ventilation in ventilation standards. Research has shown that dry and cool air is perceived as being fresh and pleasant while the same composition of a
12、ir at an elevated temperature and humidity is perceived as stale and stuffy. During inhalation it is the convective and evaporative cooling of the mucous membrane in the nose that is essential for the fresh and pleasant sensation. Warm and humid air is perceived as being stale and stuffy due to the
13、lack of nasal cooling. This may be interpreted as a local warm discomfort in the nasal cavity. The PMV model is the basis for existing thermal comfort standards. It is quite flexible and allows for the determination of a wide range of air temperatures and humidities that result in thermal neutrality
14、 for the body as a whole. But the inhaled air would be perceived as being very different within this wide range of air temperatures and humidities. An example: light clothing and an elevated air velocity or cooled ceiling, an air temperature of 28ºC and a relative humidity of 60% may give PMV=0
15、, but the air quality would be perceived as stale and stuffy. A simultaneous request for high perceived air quality would require an air temperature of 20-22oC and a modest air humidity. Moderate air temperature and humidity decrease also SBS symptoms (Krogstad et al. 1991, Andersson et al. 1975) an
16、d the ventilation requirement, thus saving energy during the heating season. And even with air-conditioning it may be beneficial and save energy during the cooling season.PMV model and the adaptive modelThe PMV model is based on extensive American and European experiments involving over a thousand s
17、ubjects exposed to well-controlled environments (Fanger 1970). The studies showed that the thermal sensation is closely related to the thermal load on the effector mechanisms of the human thermoregulatory system. The PMV model predicts the thermal sensation as a function of activity, clothing and th
18、e four classical thermal environmental parameters. The advantage of this is that it is a flexible tool that includes all the major variables influencing thermal sensation. It quantifies the absolute and relative impact of these six factors and can therefore be used in indoor environments with widely
19、 differing HVAC systems as well as for different activities and different clothing habits. The PMV model has been validated in climate chamber studies in Asia (de Dear et al. 1991; Tanabe et al. 1987) as well as in the field, most recently in ASHRAEs worldwide research in buildings with HVAC systems
20、 that were situated in cold, temperate and warm climates and were studied during both summer and winter (Cena et al. 1998; Donini et al. 1996; de Dear et al. 1993a; Schiller et al. 1988). The PMV is developed for steady-state conditions but it has been shown to apply with good approximation at the r
21、elatively slow fluctuations of the environmental parameters typically occurring indoors. Immediately after an upward step-wise change of temperature, the PMV model predicts well the thermal sensation, while it takes around 20 min at temperature down-steps (de Dear et al. 1993b).Field studies in warm
22、 climates in buildings without air-conditioning have shown, however, that the PMV model predicts a warmer thermal sensation than the occupants actually feel (Brager and de Dear 1998). For such non-air-conditioned buildings an adaptive model has been proposed (de Dear and Brager 1998). This model is
23、a regression equation that relates the neutral temperature indoors to the monthly average temperature outdoors. The only variable is thus the average outdoor temperature, which at its highest may have an indirect impact on the human heat balance. An obvious weakness of the adaptive model is that it
24、does not include human clothing or activity or the four classical thermal parameters that have a well-known impact on the human heat balance and therefore on the thermal sensation. Although the adaptive model predicts the thermal sensation quite well for non-air-conditioned buildings of the 1900s lo
25、cated in warm parts of the world, the question remains as to how well it would suit buildings of new types in the future where the occupants have a different clothing behaviour and a different activity pattern.Why then does the PMV model seem to overestimate the sensation of warmth in nonair-conditi
26、oned buildings in warm climates? There is general agreement that physiological acclimatization does not play a role. One suggested explanation is that openable windows in naturally ventilated buildings should provide a higher level of personal control than in air-conditioned buildings. We do not bel
27、ieve that this is true in warm climates. Although an openable window sometimes may provide some control of air temperature and air movement, this applies only to the persons who work close to a window. What happens to persons in the office who work far away from the window? And in warm climates, the
28、 normal strategy in naturally ventilated buildings is to cool the building during the night and then close the windows some time during the morning when the outdoor temperature exceeds the indoor temperature. Another obstacle is of course traffic noise, which makes open windows in many areas impossi
29、ble. We believe that in warm climates air-conditioning with proper thermostatic control in each space provides a better perceived control than openable windows.Another factor suggested as an explanation to the difference is the expectations of the occupants. We think this is the right factor to expl
30、ain why the PMV overestimates the thermal sensation of occupants in non-air-conditioned buildings in warm climates. These occupants are typically people who have been living in warm environments indoors and outdoors, maybe even through generations. They may believe that it is their “destiny” to live
31、 in environments where they feel warmer than neutral. If given a chance they may not on average prefer an environment that is different from that chosen by people who are used to air-conditioned buildings. But it is likely that they would judge a given warm environment as less severe and less unacce
32、ptable than would people who are used to air-conditioning. This may be expressed by an expectancy factor, e, to be multiplied with PMV to reach the mean thermal sensation vote of the occupants of the actual non-air-conditioned building in a warm climate. The factor e may vary between 1 and 0.5. It i
33、s 1 for air-conditioned buildings. For non-air-conditioned buildings, the expectancy factor is assumed to depend on the duration of the warm weather over the year and whether such buildings can be compared with many others in the region that are air-conditioned. If the weather is warm all year or mo
34、st of the year and there are no or few other air-conditioned buildings, e may be 0.5, while it may be 0.7 if there are many other buildings with air-conditioning. For non-air-conditioned buildings in regions where the weather is warm only during the summer and no or few buildings have air-conditioni
35、ng, the expectancy factor may be 0.7 to 0.8, while it may be 0.8 to 0.9 where there are many air-conditioned buildings. In regions with only brief periods of warm weather during the summer, the expectancy factor may be 0.9 to 1. Table 1 proposes a first rough estimation of ranges for the expectancy
36、factor corresponding to high, moderate and low degrees of expectation.Table 1. Expectancy factors for non-air-conditioned buildings in warm climates.ExpectationClassification of buildingsExpectancyfactor, eHighNon-air-conditioned buildings located in regions where air-conditioned buildings are commo
37、n. Warm periods occurring briefly during the summer season.0.9 - 1.0ModerateNon-air-conditioned buildings located in regions with some air-conditioned buildings. Warm summer season.0.7 - 0.9LowNon-air-conditioned buildings located in regions with few air-conditioned buildings. Warm weather during al
38、l seasons.0.5 - 0.7A second factor that contributes erroneously to the difference between the PMV and actual thermal sensation votes in non-air-conditioned buildings is the estimated activity. In many field studies in offices, the metabolic rate is estimated on the basis of a questionnaire identifyi
39、ng the percentage of time the person was sedentary, standing, or walking. This mechanistic approach does not acknowledge the fact that people, when feeling warm, unconsciously tend to slow down their activity. They adapt to the warm environment by decreasing their metabolic rate. The lower pace in w
40、arm environments should be acknowledged by inserting a reduced metabolic rate when calculating the PMV.To examine these hypotheses further, data were downloaded from the database of thermal comfort field experiments (de Dear 1998). Only quality class II data obtained in non-air-conditioned buildings
41、 during the summer period in warm climates were used in the analysis. Data from four cities (Bangkok, Brisbane, Athens, and Singapore) were included, representing a total of more than 3200 sets of observations (Busch 1992, de Dear 1985, Baker 1995, de Dear et al. 1991). The data from these four citi
42、es with warm climates were also used for the development of the adaptive model (de Dear and Brager 1998).For each set of observations, recorded metabolic rates were reduced by 6.7% for every scale unit of PMV above neutral, i.e. a PMV of 1.5 corresponded to a reduction in the metabolic rate of 10%.
43、Next, the PMV was recalculated with reduced metabolic rates using ASHRAEs thermal comfort tool (Fountain and Huizenga 1997). The resulting PMV values were then adjusted for expectation by multiplication with expectancy factors estimated to be 0.9 for Brisbane, 0.7 for Athens and Singapore and 0.6 fo
44、r Bangkok. As an average for each building included in the field studies, Figure 1 and Table 2 compare the observed thermal sensation with predictions using the new extended PMV model for warm climates.Figure 1. Thermal sensation in non-air-conditioned buildings in warm climates. Comparison of obser
45、ved mean thermal sensation with predictions made using the new extension of the PMV model for non-air-conditioned buildings in warm climates. The lines are based on linear regression analysis weighted according to the number of responses obtained in each building.CityExpectancyfactorPMV adjusted top
46、roper activityPMVe adjustedfor expectationObservedmean voteBangkok0.62.01.21.3Singapore0.7Athens0.71.00.70.7Brisbane0.8Table 2. Non-air-conditioned buildings in warm climates.Comparison of observed thermal sensation votes and predictions made using the new extension of the PMV mode
47、l.The new extension of the PMV model for non-air-conditioned buildings in warm climates predicts the actual votes well. The extension combines the best of the PMV and the adaptive model. It acknowledges the importance of expectations already accounted for by the adaptive model, while maintaining the
48、 PMV models classical thermal parameters that have direct impact on the human heat balance. It should also be noted that the new PMV extension predicts a higher upper temperature limit when the expectancy factor is low. People with low expectations are ready to accept a warmer indoor environment. Th
49、is agrees well with the observations behind the adaptive model.Further analysis would be useful to refine the extension of the PMV model, and additional studies in non-air-conditioned buildings in warm climates in different parts of the world would be useful to further clarify expectation and accept
50、ability among occupants. It would also be useful to study the impact of warm office environments on work pace and metabolic rate.Conclusions The PMV model has been validated in the field in buildings with HVAC systems, situated in cold, temperate and warm climates and studied during both summer and
51、winter. In non-air-conditioned buildings in warm climates, occupants may perceive the warmth as being less severe than the PMV predicts, due to low expectations. An extension of the PMV model that includes an expectancy factor is proposed for use in non-air-conditioned buildings in warm climates. Th
52、e extended PMV model agrees well with field studies in non-air-conditioned buildings in warm climates of three continents. A future search for excellence will demand that all persons in a space be thermally comfortable. This requires individual thermal control. Thermal comfort and air quality in a b
53、uilding should be considered simultaneously. A high perceived air quality requires moderate air temperature and humidity.AcknowledgementFinancial support for this study from the Danish Technical research Council is gratefully acknowledged.ReferencesAndersson, L.O., Frisk, P., Löfstedt, B., Wyon
54、, D.P., (1975), Human responses to dry, humidified and intermittently humidified air in large office buildings. Swedish Building Research Document Series, D11/75.ASHRAE 55-1992: Thermal environmental conditions for human occupancy. American Society of Heating, Refrigerating and Air-conditioning Engi
55、neers, Inc.Baker, N. and Standeven, M. (1995), A Behavioural Approach to Thermal Comfort Assessment in Naturally Ventilated Buildings. Proceedings from CIBSE National Conference, pp 76-84.Brager G.S., de Dear R.J. (1998), Thermal adaptation in the built environment: a literature review. Energy and B
56、uildings, 27, pp 83-96.Busch J.F. (1992), A tale of two populations: thermal comfort in air-conditioned and naturally ventilated offices in Thailand. Energy and Buildings, vol. 18, pp 235-249.CEN ISO 7730-1994: Moderate thermal environments - Determination of the PMV and PPD indices and specificatio
57、n of the conditions for thermal comfort. International Organization for Standardization, Geneva.Cena, K.M. (1998), Field study of occupant comfort and office thermal environments in a hot-arid climate. (Eds. Cena, K. and de Dear, R.). Final report, ASHRAE 921-RP, ASHRAE Inc., Atlanta.de Dear, R., Fo
58、untain, M., Popovic, S., Watkins, S., Brager, G., Arens, E., Benton, C., (1993a), A field study of occupant comfort and office thermal environments in a hot humid climate. Final report, ASHRAE 702 RP, ASHRAE Inc., Atlanta.de Dear, R., Ring, J.W., Fanger, P.O. (1993b), Thermal sensations resulting fr
59、om sudden ambient temperature changes. Indoor Air, 3, pp 181-192.de Dear, R. J., Leow, K. G. and Foo, S.C. (1991), Thermal comfort in the humid tropics: Field experiments in air-conditioned and naturally ventilated buildings in Singapore. International Journal of Biometeorology, vol. 34, pp 259-265.de Dear, R.J. (1998), A global database of thermal comfort field experiments. ASHRAE Transactions, 104(1b), pp 1141-1152.de Dear,
溫馨提示
- 1. 本站所有資源如無(wú)特殊說(shuō)明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒(méi)有圖紙預(yù)覽就沒(méi)有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 2024年江蘇省鹽城市第二小學(xué)數(shù)學(xué)三上期末質(zhì)量檢測(cè)模擬試題含解析
- 七年級(jí)下冊(cè)各單元綜合性學(xué)習(xí)課件
- 八年級(jí)生物上《細(xì)菌》-課件
- 自考行政管理的行業(yè)前景試題及答案
- 2025年護(hù)士專業(yè)定位試題及答案挖掘
- 執(zhí)業(yè)護(hù)士備考中的知識(shí)點(diǎn)掌握試題及答案
- 執(zhí)業(yè)藥師考試模擬試題及答案解析
- 中國(guó)古典文學(xué)對(duì)管理的啟示試題及答案
- 行政管理專業(yè)學(xué)生的職業(yè)發(fā)展規(guī)劃試題及答案
- 執(zhí)業(yè)護(hù)士執(zhí)業(yè)技能要求試題及答案2025
- 2025年度麻醉科人才培養(yǎng)計(jì)劃
- 2025年春新人教版語(yǔ)文一年級(jí)下冊(cè)教學(xué)課件 14 文具的家
- 2025-2031年中國(guó)電競(jìng)俱樂(lè)部行業(yè)市場(chǎng)需求預(yù)測(cè)及投資規(guī)劃建議報(bào)告
- 學(xué)校環(huán)境對(duì)兒童心理健康的積極影響
- 2025年中國(guó)石油集團(tuán)招聘筆試參考題庫(kù)含答案解析
- 智能制造能力成熟度模型(-CMMM-)介紹及評(píng)估方法分享
- 網(wǎng)絡(luò)協(xié)議優(yōu)化與適配-洞察分析
- 市場(chǎng)營(yíng)銷試題(含參考答案)
- 重慶市2023年度居民健康狀況報(bào)告
- (輸血科)培訓(xùn)計(jì)劃
- 機(jī)械工程技術(shù)訓(xùn)練知到智慧樹(shù)章節(jié)測(cè)試課后答案2024年秋北京航空航天大學(xué)
評(píng)論
0/150
提交評(píng)論